Temperature Transmitters

Precision 4-20mA transmitters for accurate temperature sensing over long distances

Temperature Transmitter Description

BAPI's temperature transmitters incorporate a 1KΩ RTD sensor and an amplifier. These devices provide an accurate two wire, 4 to 20mA output over a specified temp range. They are specifically designed for long distance transmission over long distances without degradation of the 4 to 20mA signal. 100Ω units also available upon request.

Each temperature transmitter is not configurable for its specified temp range. If you don't offer the right transmitter at the field or the light transmitter in Class A RTD's to improve overall accuracy. The specified unit at the calibrated range offers better accuracy to minimize the cross on the control components. Use the accuracy of the matched pair unit becomes a function of the transfer linearity (RTD curve) and reference transmitter somewhat.

Standard units will offset 0–100°F ( commonly found ) - Reference Thermometer (example) :

Offset Range units : –20°C to +250°C (-4°F to 482°F)
Max.Span : 16.6°C (30°F) – 2.0 to +600°C (–148°F to +1000°F)

BA/TM- 1K in (0-30°F)
Spec : +/- 0.08˚C (0.14˚F) = 16°F] MAX
BA/TM- 1K in (0-100°F)
Spec : +/- 0.10˚C (0.18˚F) = 38-55°F] OFFSET

These accuracies are for the worst range of the sensor, although the accuracies in the midpoint of the sensor will be tighter. Run these over your BAPI representative for details.

BAPI temperature transmitters come in a ruggedized package for all non-room configurations where moisture or condensation may be a problem. The potting material used to ruggedize the transmitters has a high thermal conductivity to eliminate circuit overheating and allow thermal expansion to minimize the stress on the control components. Due to the extremely low moisture absorption properties of the epoxy, a ruggedized transmitter will remain operational even if temporarily immersed in water.

Specifications

Sensor

1000Ω Platinum RTD

Supply Voltage

12 to 40 VDC

Output

4 to 20 mA, 0 to 5V, 1 to 5V, 0 to 10V, 2 to 10V

Max. Loop Resistance

850Ω at 24VDC

Span

Min 16.6°C (30°F), Max 555°C (1000°F)

Zero

Min -100°C (-148°F), Max 482°C (900°F)

System Accuracy

±0.065% of Span

Linearity

±(0.125 x T-20ºC)/100

Operational Humidity

0 to 95%, non-condensing

Output Current Limits

Less than 1mA and 22.35 ± 0.15 mA

Power Output Shift

±0.009% of Span to 40VDC

Connections

Four 22-gauge etched Teflon leads or terminal blocks

Operating Temperature

Transmitter:-20 to 70°C
Sensor (standard):-65 to 105°C
Sensor (available):-200 to 600°C

0-100 °F Temperature Transmitter Output Table

°F°CmA
0-17.784.000
1-17.224.160
2-16.674.320
3-16.114.480
4-15.564.640
5-15.004.800
6-14.444.960
7-13.895.120
8-13.335.280
9-12.785.440
10-12.225.600
11-11.675.760
12-11.115.920
13-10.566.080
14-10.006.240
15-9.446.400
16-8.896.560
17-8.336.720
18-7.786.880
19-7.227.040
20-6.677.200
21-6.117.360
22-5.567.520
23-5.007.680
24-4.447.840
25-3.898.000
26-3.338.160
27-2.788.320
28-2.228.480
29-1.678.640
30-1.118.800
31-0.568.960
320.009.120
330.569.280
341.119.440
351.679.600
362.229.760
372.789.920
383.3310.080
393.8910.240
404.4410.400
415.0010.560
425.5610.720
436.1110.880
446.6711.040
457.2211.200
467.7811.360
478.3311.520
488.8911.680
499.4411.840
5010.0012.000
°F°CmA
5110.5612.160
5211.1112.320
5311.6712.480
5412.2212.640
5512.7812.800
5613.3312.960
5713.8913.120
5814.4413.280
5915.0013.440
6015.5613.600
6116.1113.760
6216.6713.920
6317.2214.080
6417.7814.240
6518.3314.400
6618.8914.560
6719.4414.720
6820.0014.880
6920.5615.040
7021.1115.200
7121.6715.360
7222.2215.520
7322.7815.680
7423.3315.840
7523.8916.000
7624.4416.160
7725.0016.320
7825.5616.480
7926.1116.640
8026.6716.800
8127.2216.960
8227.7817.120
8328.3317.280
8428.8917.440
8529.4417.600
8630.0017.760
8730.5617.920
8831.1118.080
8931.6718.240
9032.2218.400
9132.7818.560
9233.3318.720
9333.8918.880
9434.4419.040
9535.0019.200
9635.5619.360
9736.1119.520
9836.6719.680
9937.2219.840
10037.7820.000

Field Adjustments

Each transmitter is calibrated to the specified temperature range that is ordered. Field adjustments are not available. If adjustments are needed, please contact your BAPI representative.

Need a Temperature Transmitter?

Our T1K transmitters provide accurate 4-20mA signals for long-distance temperature measurement applications.